Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T08CM03574
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2009 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
10/15/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) OK TO USE KITCHEN 2) BANDING ON 2ND LAYER OF WRAP NOT WITHIN 1 1/2" OF EDGE INSTALL APPLIANCES 3) AIR BALANCE EXHAUST FANS 4) NEED TO TEST AUTOMATIC OPERATION OF FAN |
|
10/14/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) CHECKED 1ST LAYER OF FIRE WRAP BOTH DUCTS 2) OK FOR 2ND LAYER 3) OK TO COMPLETE ANSUL SYSTEM |
|
10/13/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
10/09/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PLEASE ADDRESS CODE ISSUES ON 4 EXISTING A/C UNITS 2) CHECKED WELDS ON GREASE DUCTS-OK FOR 1ST LAYER OF FIRE WRAP 3) OVERHEAD CONDENSATE PIPING OK |
|
10/08/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* |