Permit: T08CM03574

Parcel: 110162190


Addresses:

6255 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
11/30/2009 MECHANICAL - HOODS Approved IVRS - Inspection :*
10/15/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) OK TO USE KITCHEN
2) BANDING ON 2ND LAYER OF WRAP NOT WITHIN 1 1/2" OF EDGE INSTALL APPLIANCES
3) AIR BALANCE EXHAUST FANS
4) NEED TO TEST AUTOMATIC OPERATION OF FAN
10/14/2009 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
1) CHECKED 1ST LAYER OF FIRE WRAP BOTH DUCTS
2) OK FOR 2ND LAYER
3) OK TO COMPLETE ANSUL SYSTEM
10/13/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
10/09/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) PLEASE ADDRESS CODE ISSUES ON 4 EXISTING A/C UNITS
2) CHECKED WELDS ON GREASE DUCTS-OK FOR 1ST LAYER OF FIRE WRAP
3) OVERHEAD CONDENSATE PIPING OK
10/08/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*