Permit: T08CM03574

Parcel: 110162190


Addresses:

6255 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/30/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
11/03/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL A/C EQUIPMENT REMOVED FOR RE-ROOFING NEEDS TO BE RE-INSTALLED TO MEET CURRENT CODES. THIS INCLUDES ANY UNITS THAT HAVE BEEN ALTERED
10/08/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL PVC CONDENSATE PIPING TO HAVE PURPLE PRIMER APPLIED PRIOR TO GLUING FITTINGS
2) PROVIDE 20 GA. ELBOWS ON OVER VENTING
3) SEAL SEAMS
4) PROVIDE A CONDENSATE DRAIN ON PAN WASHER VENT
5) CHECKED WELDS ON 1 GREASE DUCT
6) OK FOR 1ST LAYER OF FIRE WRAP
7) OK FOR CEILING TILES IN BAKERY
09/02/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK FOR FINAL IN RECEIVING AREA
07/30/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
FINISH TERMINATION OF REFRIGERANT RELIEF VENTS.
OK TO USE PRODUCE AS OVERSTOCK MECH. ROOM
C & D OK TO USE