Permit: T08CM03574

Parcel: 110162190


Addresses:

6255 E GRANT RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM03574

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/14/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/09/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1" PIPE INSULATION REQUIRED ON ALL CIRCULATING HW SYSTEMS
10/01/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DELI WATER PIPING IN WALL TEST (ONLY)
2) HAND SINK ON SOUTHEAST SIDE OF BAKERY IN WALL TEST OK WATER AND PVC (ONLY)
3) 4 GAS DROPS IN WALL TEST NOT HOLDING ON SOUTH END GAS DROP ONLY OTHERS OK
09/30/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DISH PREP IN WALL PIPING TEST OK #113 (ONLY) PVC AND COPPER (ONLY)
2) DELI 110 VENT PIPING TEST OK (ONLY) PVC AND COPPER (ONLY)
09/29/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ROOM #112 IN WALL PIPING TEST OK (ONLY)
2) ROOM #111 WEST AND NORTH WALL IN TEST OK (ONLY)
09/28/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) MEAT PREP WEST WALL AND HANK SINK ON NORTH WALL TEST OK
09/25/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/23/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BAKERY LINE 1 FROM A TO B FROM #1 TO #2 IN WALL PIPING TEST OK (ONLY)
09/04/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/02/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) WATER NOT PER PLAN
2) PROVIDE REVISION FOR INSPECTION ISOLATE FROM METAL
3) STERILIZATION OF NEW PIPING REQ PER UPC 609. ALSO BACKFLOW CERTS
4) NEED TO INSPECT RWLS
5) PROVIDE TEST ON GAS
08/05/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
08/04/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVING AREA PLUMBING IN WALLS-OK
2) INSULATE PER PLAN, RECALL FOR ABOVE CEILING
07/31/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DWV WITH TEST IN MECH ROOMS OK
2) NEED TO INSPECT RWLS-NOTE: SUN BURNED PVC IS NOT ACCEPTABLE
3) RP REQUIRES UNIONS FOR SERVICING WITH CERT AT FINAL. SIZING ?
4) REMOVE UNLAWFUL HB CONN AT HYDRANT
5) FE THREADED PVC FITTINGS MAY NOT BE CONCEALED UPC 1.S #9 316.1.5
6) CLEANOUT EXTENSIONS SHALL BE MADE WITH WYE PATTERN FITTING 707.7
7) ALL JOINTS REQUIRE A TEST 712.2
8) ALSO SUPPORTS AND PROTECTION
06/26/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/15/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NOTE: ALL AREAS REQUIRE FINAL INSPECTION PRIOR TO USE
CALL FOR INTERMEDIATE AND FINAL INSP. OF DAIRY CASE.
06/01/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INSTALL ABOVE SLAB FITTINGS AT TIME OF ROUGH TEST