Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03574
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) ELECTRIC ON BLDG OK AND ITEMS ON LIST ALL OK |
|
01/22/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
11/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) COOLER DISCONNECT NEEDS GROUNDING BONDING GREEN SCREW AND PROPER SIZE FUSES 2) NEED BRACING FOR BLOWER BOXES, 1 NEEDS COVER, CLEAR PLASTIC COVER FOR GFI'S, NEED BUSHING FOR LIQUID TIGHT GOING INTO BLOWER |
|
11/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SECOND HALF OF ROOF M6 FLUID CONDENSOR C & D RACK, COOLER CONTROLLER PENETRATIONS ALL SEALED FOR WALK IN COOLER FOR REFRIDGERATION EQUIPMENT ONLY OK 2) NEED TO SEE EXHAUST FANS, A/C'S ALL MADE UP |
|
11/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WEST SIDE OF ROOF OK 2) MEZZANINE POWER SUPPLY PANELS OK 3) SWITCH GEAR FENCE LINE NEEDS 6' CLEARANCE 4) LOW VOLTAGE TO BE STRAPPED OR REMOVED, BOXES NEED CONNECTORS REMOVED AND PLUGED, IN FRESH LINE AREA 5) EXISTING BOXES AND PIPES, CASE COOLER AREA AGAIN NEEDS KO SEALS IN BOXES, LOW VOLTAGE STRAPPED, BREAD AREA BOXES MISSING KO SEALS, PIPE NEEDS STRAPPING OR REMOVE PIPE, AREA 122 BOXES NEED KO SEALS 6) AREA 118 LOW VOLTAGE NEEDS STRAPPING ALL THREAD FOR RACK TO BE STRAIGHTENED OUT, OUTLET TO BE REPLACED, TV AREA NEEDS PIPE TO BE STRAPPED AND LOW VOLTAGE TO BE STRPPAED, BOXES NEED KO SEALS, LADDER RACK ABOVE REQESTER AREA NEED TO SEPERATE LOW AND HIGH VOLTAGE WIRES, AGAIN LOW VOLTAGE NEEDS STRAPPING, ALSO REMOVE WIRES AND PIPE NOT BEING USED |
|
11/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) REFRIDGERATION ELECTRICAL LIGHTS AND FAN COILS IN COOLERS 2) 3105 DAIRY COOLER, #107 PRODUCE SHOP COOLER, ROTISSERIE PREP COOLER, #112, 113 DISH PREP COOLER, 116 TALL MEAT DRIVE IN COOLER, #119 TALL BAKERY FREEZER, DELI ISLAND CASES AND COLUMNS FEEDERS TO CASES, FRESH LINE CASES, CHICKEN PREP AREA, LIGHTS, WINDOWS, DISH PREP AREA, #106 MECHANICAL ROOM, #109 EQUIPMENT ROOM ALL OK 2) STILL NEED TO CHECK ROOF 3) CHICKEN PREP WINDOWS HEAT NOT HOOKED UP AT THIS TIME |