Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
01/12/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES
PROVIDE INSTALL INSTRUCTIONS FOR CONDENSATE PUMP
MAY NOT BE PLENUM RATED
PROVIDE BUSHINGS IN FAN COIL CABINETS AT REFER LINES
01/02/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) DUCT SMOKE DETECTOR NOT IN PROPER LOCATION IN REFERENCE TO RETURN AND OSA INLETS
2) COMBUSTIBLE MATERIAL IN PLENIUM-PVC, WOOD, ETC...
3) DUCTS RESTING ON SPRINKLER PIPING
4) BUILDER LOOKING FOR LETTER ALLOWING STRAIGHT TAPS IN LIEU OF HIGH E
12/30/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*