Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/12/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES PROVIDE INSTALL INSTRUCTIONS FOR CONDENSATE PUMP MAY NOT BE PLENUM RATED PROVIDE BUSHINGS IN FAN COIL CABINETS AT REFER LINES |
|
| 01/02/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR NOT IN PROPER LOCATION IN REFERENCE TO RETURN AND OSA INLETS 2) COMBUSTIBLE MATERIAL IN PLENIUM-PVC, WOOD, ETC... 3) DUCTS RESTING ON SPRINKLER PIPING 4) BUILDER LOOKING FOR LETTER ALLOWING STRAIGHT TAPS IN LIEU OF HIGH E |
|
| 12/30/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |