Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* TESTED DUCT SMOKE DETECTORS OK FOR FINAL |
|
| 01/15/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/14/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INSTALL DUCT SMOKE DETECTORS IN THE RETURN PLENUM |
|
| 12/18/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* COMMON RETURN AIR PLENUM IN EXCESS OF 2000 CFM REQUIRES A DUCT SMOKE DETECTION SYSTEM AT EACH UNIT SEE SECTION 606.2.2 2006 IMC |