Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T08CM03532
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2009 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 12/16/2008 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO OPEN SOFFIT TO INSPECT CONNECTION TO HORIZONTAL BEAM TO RAFTERS 2) DRAWING CALLS FOR 2 X 10 RAFTERS. OWNER HAS USED 2 X 6-NEED TO APPEAL TO BLDG OFFICIAL OR COMPLY 3) NEED MORE NAILS IN T-11'S SIDING 4) EXPOSE TREATED SOLE PLATE TO VERIFY AND VERIFY H.25 EACH STUD 5) 3 RECEPTACLES ARE SHOWING OPEN GROUND-NEED TO HAVE A LICENSED ELECTRICIAN TO INSPECT ADDITION AND GIVE A CERTIFIED LETTER, STATING THAT ALL WIRING IS TO CODE |