Permit: T08CM03517

Parcel: 11207156B


Addresses:

2470 N TUCSON BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/17/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES PREVIOUS INSPECTION - MC CABLE
06/12/2009 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT MC PER 300.11
2. HANDY BOXES OVERFILLED
3. SUPPORT VDV CABLING UP OFF OF DUCTS & GRID
725.3 & 24, 800.3 & 24, 300.11
4. CEILING CLOSED WITHOUT APPROVAL PLEASE RE-OPEN TO INSPECT
06/10/2009 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
MC CABLE ABOVE CEILING TO BE
PROPERLY SECURED/SUPPORTED