Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/17/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES PREVIOUS INSPECTION - MC CABLE |
|
| 06/12/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC PER 300.11 2. HANDY BOXES OVERFILLED 3. SUPPORT VDV CABLING UP OFF OF DUCTS & GRID 725.3 & 24, 800.3 & 24, 300.11 4. CEILING CLOSED WITHOUT APPROVAL PLEASE RE-OPEN TO INSPECT |
|
| 06/10/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* MC CABLE ABOVE CEILING TO BE PROPERLY SECURED/SUPPORTED |