Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03508
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT VDV CABLING PER 725.24, 800.24, 300.11 OK TO TILE AFTER CORRECTIONS |
|
11/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. MC CABLE TO BE SUPPORTED WITH 12" OF TERM. AND AT 6' INTERVAL PER NEC. SUPPORT WIRES TO BE TIED OFF AT BOTH ENDS -- 300.11 NEC 2. OK WALLS |