Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM03502
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* THIS INSPECTION FOR CLOSET FLANGE OK |
|
| 12/05/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER WALLS AFTER INSTALLING 2 MISSING FHA STRAPS, AND SECURING CW ABOVE SINK. USE CLAMPS IN THE MANNER INTENDED 2. CALL FOR INSP. OF CLOSET FLANGE PRIOR TO SETTING WC ARTISTIC PLUMBING |
|
| 12/01/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT AND PROTECT ABS AT METAL STUDS OFFSET WATER PIPING AT MS WALL BRACKET, INSTALL BACKING AND INSULATE HW CONNECT VENT DWV W/TEST OK 906-0754 |
|
| 11/26/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT AND SECURE PIPING IN WALLS AND OVER HEAD PER UPC T-3 2) ISOLATE PLASTIC FROM SHARP METAL, ISOLATE AND SECURE COPPER. USE APPROVED CLAMPS IN THE CORRECT POSITION 3) CARRIER SPECIFIED FOR LAV 4) BACKING FOR MS 5) NAIL PROTECTION ON PIPING WITHIN 1 1/4 OF STUD FACE |