Permit: T08CM03496

Parcel: 116212080


Addresses:

31 N SILVERBELL RD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/14/2009 BUILDING - FINAL Approved IVRS - Inspection :*
1) COMPLETE ON CONDITION WHEN TEMP HANDRAILS ARE REPLACED WITH PERMANENT RAILS, PLEASE CALL 909-5176 FOR INSPECTION
07/13/2009 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PORCH LIGHTS PLATED OF (FIXTURE REMOVED)
2) ITEMS NOT COMPLETE
07/10/2009 BUILDING - FINAL Partial Approval IVRS - Inspection :*
ELECTRIC:
1) NO LOX ON AL. CONDUCTORS SERV./SUB PANEL
2) #8 CY. REQUIRES MAX 50/50 BREAKER A/C
3) BOND GRD BUSS TO SUB/CABINET
4) CONNECT H20 HTR
5) COMPLY WITH LIGHTING CODE FULL CUT OFF AT FRONT ENTRY
MECHANICAL:
1) FINISH CONDENSATE
2) NEED SECONDARY LINE OR ELECT. SENSOR TO SHUT DOWN UNIT FOR OVERFLOW
3) REMOVE TAPE SINGLE TO DBL WALL ADD 3 SCREWS MIN.
BLDG:
1) ALL HAND AND GUARD RAILS
2) WILL CHECK FOR GUARD RAIL FOR WALKING DECK
3) HOUSE ADDRESS NUMBERS
PLUMBING:
1) FINISH T & P LINE
2) PROTECT AND FINISH CLEANOUTS AB'S
NOTE:
1) I WILL LOOK FOR ? ON GUARD HEIGHT AT BALCONY