Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) COMPLETE ON CONDITION WHEN TEMP HANDRAILS ARE REPLACED WITH PERMANENT RAILS, PLEASE CALL 909-5176 FOR INSPECTION |
|
| 07/13/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PORCH LIGHTS PLATED OF (FIXTURE REMOVED) 2) ITEMS NOT COMPLETE |
|
| 07/10/2009 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* ELECTRIC: 1) NO LOX ON AL. CONDUCTORS SERV./SUB PANEL 2) #8 CY. REQUIRES MAX 50/50 BREAKER A/C 3) BOND GRD BUSS TO SUB/CABINET 4) CONNECT H20 HTR 5) COMPLY WITH LIGHTING CODE FULL CUT OFF AT FRONT ENTRY MECHANICAL: 1) FINISH CONDENSATE 2) NEED SECONDARY LINE OR ELECT. SENSOR TO SHUT DOWN UNIT FOR OVERFLOW 3) REMOVE TAPE SINGLE TO DBL WALL ADD 3 SCREWS MIN. BLDG: 1) ALL HAND AND GUARD RAILS 2) WILL CHECK FOR GUARD RAIL FOR WALKING DECK 3) HOUSE ADDRESS NUMBERS PLUMBING: 1) FINISH T & P LINE 2) PROTECT AND FINISH CLEANOUTS AB'S NOTE: 1) I WILL LOOK FOR ? ON GUARD HEIGHT AT BALCONY |