Permit: T08CM03470

Parcel: 11301146Z


Addresses:

1767 E PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM03470

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/06/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
04/30/2009 PLUMBING - FINAL Not ready for Inspection 1. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO CALLING "FINAL"
2. CORRECTIONS MADE AT BAKERY OK
04/29/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAND SINK AT BAKERY; CAULK SINK
2. FILL IN VOIDS AROUND PIPES
3. REMOVE REVERSED TEST PLUG; INSTALL COUNTER SUNK TAPPED PLUG W/MACHINE SCREW
04/08/2009 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEPARATE NON-CARBONATED BEVERAGES FROM CARBONATED
2. SUPPORT BACKFLOW DEVICES W/AIR GAP
3. SUPPORT MEAT CASE DRAIN W/1" AIR GAP AND USE APPROVED PIPE SUPPORTS ON BEVERAGE DRAINS

NOTE: FLOOR SINK MAY NOT MEET MIN. ACCESS REQUIREMENTS
04/02/2009 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. STARBUCKS COMPLETE.
2. OCCUPANCY IS DEPENDENT ON
PERMISSION FROM BUILDING INSPECTOR
04/01/2009 PLUMBING - FINAL Not ready for Inspection 1. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS
2. COMPLETE ALL CORRECTIONS PREVIOUSLY NOTED
3. AT STARBUCKS:
- TRAP ARM MAY NOT CHANGE SIZE (CHAPTER 10 2006 UPC)
- TRAP AND TRAP ARM TO BE THE SAME SIZE
- CLEANOUTS REQUIRE 12" CLEARANCE IN FRONT
- ALL INDIRECT WASTE PIPING REQUIRES MINIMUM 1" AIR GAP
- DRAINAGE PIPING TO BE LONG TURN RADIUS
03/31/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/26/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. ELEVATED WATER HEATER REQUIRES DRIP PAN
2. PROVIDE INSULATION ON HOT & COLD 8' IN & OUT OK
WATER HEATER PER 2006 I.E.C.C REQUIREMENTS
3. SUPPORT EXPANSION TANK AND REMOVE EXPANSION TANK SHUT OFF VALVE, 2-COMPS REQUIRE CORRECT DRAINAGE
4. 3-COMP SINK REQUIRES SEPARATE INDIRECT DRAIN FOR SANITIZE BOWL
5. PROVIDE MINIMUM 1" AIR GAP AT INDIRECT DRAIN TERMINATIONS
6. PROVIDE BACKFLOW CERTIFICATIONS
7. PROVIDE FACTORY TAPPED C/O PLUGS & MACHINE SCREWS
FOR C/O COVERS
8. COMPLETE INSTALL OF ALL APPLIANCES THAT HAVE PLUMBING CONNECTIONS
9. ALL DRAINS TO HAVE MINIMUM FALL AND BE OF APPROVED MATERIALS
03/25/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/25/2009 PLUMBING - FINAL Cancelled CANCELLED PER CONTRACTOR JIM DEHORTY #602-702-2502