Permit: T08CM03470

Parcel: 11301146Z


Addresses:

1767 E PRINCE RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM03470

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2009 PLUMBING - ROUGH, SOIL Approved
03/17/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
03/16/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
STARBUCKS SOIL PIPING OK
PROVIDE DRAIN CONN. FOR 3-COMP SINK
OK TO WET VENT WITH 3" ABOVE FS
03/12/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" ABS SCH40 BRANCH FROM P.O.C AT EXISTING 4" TO STARBUCKS AREA ONLY. NO PIPING IN STARBUCKS HAS BEEN INSTALLED. OK TO COVER.
03/10/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. FLOOR SINK AT BAKERY UNDER SLAB ONLY
2. CORRECT BACKPITCHED SECTION OF VENT
VENTS BELOW FLOOD RIM TO HAVE 1/4" PITCH
3. REQUIRE FULL SIZE CLEANOUT FOR 3" FLOOR SINK
4. 2" HAND SINK UNDER SLAB AT BAKERY OK TO COVER
02/25/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
THREE FLOOR SINKS IN PRODUCE PREP AREA INSTALLED OK
OK TO COVER
02/24/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
FLOOR SINK IN PRODUCEOK TO COVER
TEST TO TEN FEET OK
P.O.C TO EXISTING OK
02/19/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. FLORAL IS COMPLETE. OK TO OCCUPY SUBJECT TO BLDG. INSPECTOR
2. CWV IN PRODUCE AREA OK TO COVER
02/12/2009 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ISLAND SINK VENT TAKE OFF REQUIRED TO BE A WYE PATTERN FITTING. SEE ILLISTRATED TRAINING MANUAL. COPIES GIVEN
2) INSTALL FOOT VENT CLEANOUT NOW SO THAT NO JOINT GOES UNTESTED
3) DEMOED SINK DRAIN NEEDS TO HAVE TEMP CAP TO PREVENT SEWER GASES FROM ENTERING STORE
4) FAILURE TO COMPLY WILL RESULT IN REINSPECTION FEES
02/12/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) PAID AFTER HOURS INSPECTION REQUESTED BY JIM WITH DEHORTY CONTR.
2) PAID WITH MONEY GRAM 6834735999
3) JIM W/ DEHORTY 602-403-9850
4) ISLAND VENT FOR FLORAL; CORRECTIONS OK
5) ABS SLEEVE IN PLACE
6) INSTALL TEST TEES IN CORRECT DIRECTION OF FLOW
7) INSTALL FOAM WRAPS
02/10/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
ADDRESS NOT POSTED - SAFEWAY
FS AT CHEESE ISLAND, OK
FS AT COLS. D/2 OK
WRAP PIPING PENETRATING CONCRETE
KEEP ALL OPEN PIPES CAPPED DURING CONSTRUCTION