Permit: T08CM03470

Parcel: 11301146Z


Addresses:

1767 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03470

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/15/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/14/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANELS NEED TO BE CLEANED AND WIRES CAPPED OR REMOVED
2) NEED KO-SEALS ON 4-SQ BOX AND TIME CLOCK
3) NEED 1/2 PIPE REMOVED AND 1/2 PIPES NEED BOXES OR CAPPED OFF
4) CALL BACK FOR REINSPECTION
03/27/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
03/25/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
03/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
STARBUCKS:
1. SUPPORT M/C CABLES UP OFF OF GRID
AS PER 330.30 & 300.11
2. SUPPORT OR REMOVE VDV CABLING
725.3 & 24, 800.3 & 24, 300.11
3. ATTACH FIXTURES TO GRID 410.16

DELI: OK DELI COUNTER CASES - OK OLIVE BAR
1. NEED FLOOR BOX COVER

*NEED ABOVE CEILING INSPECTIONS TO
START WEEK OF 3/23/09

NEED AS-BUILT FOR ELECTRIC SHWOING CIRCUITRY, LOADS, PANEL INFO, LOCATIONS AND ALL ELECTRICAL AS INSTALLED TO BE STAMPED AND APPROVED BEFORE FINAL INSPECTION IS RELEASED.
03/18/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BAKERY LINE-UP CASES
OK PVC CONDUIT FOR OLIVE BAR

1. MODIFICATION IN FIELD TO SWITCHBOARD WILL NEED NRTL FIELD EVALUATION TO RE-CERTIFY EQUIPMENT.
03/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/10/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
03/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ONE TIME ONLY FOR PVC COVERED WITHOUT INSPECTION TO ORGANIC PRODUCE CASE - NEXT TIME CONDUIT WILL BE EXPOSED TO INSPECT
2. FINISH SUPPORTING M/C AT PRODUCE CASE - OK MAKE UP AND CONNECTIONS
3. OPEN UP TILE TO INSPECT NEW LIGHTS PRODUCE/CAFE/OUTSIDE EDGES
02/20/2009 ELECTRIC - FINAL Partial Approval OK FLORAL
RECEIVED MONEY ORDER #68347351556 - $150.00
02/19/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FLORAL:
1. SUPPORT MC CABLE UP OFF OF GRID AS PER CODES
2. FILL UNUSED OPENINGS IN BOXES - NOT EMPTY FITTINGS
3. TIGHTEN LFNMC FITTINGS
4. BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
5. NEED TERMINAL ENDS WITH STRANDED CONDUCTORS
6. RECEPTACLES NOT TO BE SUPPORTED BY CENTER SCREW
7. VDV CABLING TO BE AS PER 725.3 & 24, 800.3 & 24, 300.11
8. SUPPORT TRAC FIXTURES 1 WIRE PER 4' SECTION 410
9. DISCONNECTING MEANS NEEDED FOR WALK IN CONDENSOR
10. SEAL WALK-IN RACEWAYS PER 300.7
11. JUNCTION BOX ABOVE WALK-IN TO BE ACCESSIBLE AND EXPOSED CONDUCTORS

DO NOT USE FLORAL
OK CUSTOMER SERVICE AND MANAGER OFFICE
AFTER CORRECTIONS
02/17/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
BOND JUNCTION BOXES 250.148
OK DELI CASES AFTER CORRECTIONS
OK PVC EXTENSION DAIRY CASE

*DO NOT ENERGIZE EQUIPMENT WITHOUT CLEARANCES
PARTIAL FINALS