Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03470
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/15/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/14/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PANELS NEED TO BE CLEANED AND WIRES CAPPED OR REMOVED 2) NEED KO-SEALS ON 4-SQ BOX AND TIME CLOCK 3) NEED 1/2 PIPE REMOVED AND 1/2 PIPES NEED BOXES OR CAPPED OFF 4) CALL BACK FOR REINSPECTION |
|
03/27/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/26/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
03/25/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
03/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* STARBUCKS: 1. SUPPORT M/C CABLES UP OFF OF GRID AS PER 330.30 & 300.11 2. SUPPORT OR REMOVE VDV CABLING 725.3 & 24, 800.3 & 24, 300.11 3. ATTACH FIXTURES TO GRID 410.16 DELI: OK DELI COUNTER CASES - OK OLIVE BAR 1. NEED FLOOR BOX COVER *NEED ABOVE CEILING INSPECTIONS TO START WEEK OF 3/23/09 NEED AS-BUILT FOR ELECTRIC SHWOING CIRCUITRY, LOADS, PANEL INFO, LOCATIONS AND ALL ELECTRICAL AS INSTALLED TO BE STAMPED AND APPROVED BEFORE FINAL INSPECTION IS RELEASED. |
|
03/18/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BAKERY LINE-UP CASES OK PVC CONDUIT FOR OLIVE BAR 1. MODIFICATION IN FIELD TO SWITCHBOARD WILL NEED NRTL FIELD EVALUATION TO RE-CERTIFY EQUIPMENT. |
|
03/11/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/10/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ONE TIME ONLY FOR PVC COVERED WITHOUT INSPECTION TO ORGANIC PRODUCE CASE - NEXT TIME CONDUIT WILL BE EXPOSED TO INSPECT 2. FINISH SUPPORTING M/C AT PRODUCE CASE - OK MAKE UP AND CONNECTIONS 3. OPEN UP TILE TO INSPECT NEW LIGHTS PRODUCE/CAFE/OUTSIDE EDGES |
|
02/20/2009 | ELECTRIC - FINAL | Partial Approval | OK FLORAL RECEIVED MONEY ORDER #68347351556 - $150.00 |
|
02/19/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FLORAL: 1. SUPPORT MC CABLE UP OFF OF GRID AS PER CODES 2. FILL UNUSED OPENINGS IN BOXES - NOT EMPTY FITTINGS 3. TIGHTEN LFNMC FITTINGS 4. BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 5. NEED TERMINAL ENDS WITH STRANDED CONDUCTORS 6. RECEPTACLES NOT TO BE SUPPORTED BY CENTER SCREW 7. VDV CABLING TO BE AS PER 725.3 & 24, 800.3 & 24, 300.11 8. SUPPORT TRAC FIXTURES 1 WIRE PER 4' SECTION 410 9. DISCONNECTING MEANS NEEDED FOR WALK IN CONDENSOR 10. SEAL WALK-IN RACEWAYS PER 300.7 11. JUNCTION BOX ABOVE WALK-IN TO BE ACCESSIBLE AND EXPOSED CONDUCTORS DO NOT USE FLORAL OK CUSTOMER SERVICE AND MANAGER OFFICE AFTER CORRECTIONS |
|
02/17/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BOND JUNCTION BOXES 250.148 OK DELI CASES AFTER CORRECTIONS OK PVC EXTENSION DAIRY CASE *DO NOT ENERGIZE EQUIPMENT WITHOUT CLEARANCES PARTIAL FINALS |