Permit: T08CM03470

Parcel: 11301146Z


Addresses:

1767 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T08CM03470

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2009 ELECTRIC - PROGRESS Approved
05/05/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
PANEL CHANGE HAVE COOLERS OFF FOR INSPECTION TO SEE TERMINATIONS OK
03/31/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK STARBUCKS
03/27/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK TO RE-ENERGIZE MAIN SES

1. ILLUMINATION IS NEEDED AT SES 110.26 (D)
2. TIGHTEN ALL CONDUCTOR TERMINATIONS
3. LABEL PANEL

DO NOT ENERGIZE STARBUCKS
03/26/2009 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
STARBUCKS:
1. SUPPORT RECESSED CANS TO STRUCTURE
2. FINISH ABOVE CEILING VDV CABLING AS PER PREVIOUS INSPECTION
3. NEED TO TIGHTEN LOOSE FITTINGS AT WATER HEATER, GROUND W/H ENCLOSURE
4. EXPOSED CONDUCTORS AND BOX OVERFILLED

ABOVE CEILING:
1. SECURE RECESSED CANS TO GRID AND A SUPPORT WIRE IS NEEDED
2. SECURE AND SUPPORT M/C CABLE
3. CLOSE JUNCTION BOX
03/25/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
CANCELED
03/19/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
03/18/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
03/17/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
03/16/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK 2 - 3/4" PVC CONDUIT UNDER SLAB STARBUCKS
OK ICE MACHINE MOVE AT FRONT

*NOTE: UNSCHEDULED INSPECTIONS
MAY REQUIRE A $150.00 FEE
03/12/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
03/11/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
TIGHTEN LOOSE FITTINGS PRODUCE GRAB AND GO CASE
OK AFTER CORRECTIONS
03/10/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK PVC CONDUITS AND 2 FLOOR BOXES AT BAKERY
OK ORGANIC PRODUCE CASE
OK COLUMNS DOWN FOR CASE AND RACKS
03/05/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. TIGHTEN LOOSE FITTINGS ORGANIC PRODUCE CASE
2. GROUND BOX ENCLOSURE WITH GFCI -
ORGANIC PRODUCE CASE
3. TIGHTEN FITTINGS AND STRAP CONDUIT ABOVE
PANEL "PPA"
03/04/2009 ELECTRIC - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
FLEX TERMINATION INTO WIREWAY OF EXISTING FOOD COOLER NOT CORRECT. CONNECTOR THRU KO
03/03/2009 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
02/19/2009 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
02/18/2009 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
CANCELED