Permit: T08CM03468

Parcel: 11615082A

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T08CM03468

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2010 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
09/29/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) NEED REVISION FOR RECEPTS AT KIOSK (FLORAL)
2) OK TO MOVE (ELECTRICAL) DISPLAYS
3) ELECTRIC NOT COMPLETE METAL TABLE BY SINK SHOULD HAVE GFI PROTECTED RECEPTS
09/20/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK MNGRS/CUSTOMER SERVICE NEW OFFICE
09/16/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK KIOSK, NEESD TO SUPPORT 2" VERTICAL RUN UOP COLUMN, J-BOX COVER MISSING
2) REVISE PLAN FOR FLORAL KIOSK AND RECEP OR CIRCUIT ON PLAN, ALSO 1" & 3/4" OK BELOW SLAB
3) PARTIAL FOR NEW MNGRS OFFICE, CONTR. WILL POWER CHECK AND CALL FOR INSPECTION
09/15/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) CONTRACTOR REQUEST 2:30 AM BEFORE HOURS INSPECTION
2) POWER OUTAGE FOR SES MODIFICATIONS
3) PAID CHECK #2458 FOR $330.00
4) CALLED CLEARANCE INTO MAP ROOM TEP 2:35 AM
09/02/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) SUPPORT J-BOXES ABOVE OFFICES IN FRONT OF STORE, COMPLETE MAKE UP-RECALL INSPECTION
08/31/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*