Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/20/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/15/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PD CK#978 -- $150.00 CLEARANCE TO COMBUSTIBLE MATERIAL ON 18" B-VENT OK |
|
| 05/14/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE INSULATION SHIELD AROUND B-VENT |
|
| 05/12/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES IN LIQUOR DEPT. |
|
| 05/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CONDENSATE PIPE SIZING ON MINI-SPLITS OK |
|
| 05/07/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE ACCESS TO ALL REACH IN UNITS CONDENSATE DRAINS FOR INSPECTION 2. OK FOR TILES IN SEAFOOD AREA AND LOCKERS AND OFFICE AREA CORRIDOR 3. PROVIDE SERVICE DISCONNECT FOR ALL SPLIT SYSTEMS 110V OR HIGHER 4. SIZE CONDENSATE PER C.O.T AMENDMENT |