Permit: T08CM03466

Parcel: 11901076A


Addresses:

3372 S 6TH AV


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03466

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/15/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PD CK#978 -- $150.00

CLEARANCE TO COMBUSTIBLE MATERIAL ON 18" B-VENT OK
05/14/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE INSULATION SHIELD AROUND B-VENT
05/12/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES IN LIQUOR DEPT.
05/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CONDENSATE PIPE SIZING ON MINI-SPLITS OK
05/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE ACCESS TO ALL REACH IN UNITS CONDENSATE DRAINS FOR INSPECTION
2. OK FOR TILES IN SEAFOOD AREA AND LOCKERS AND OFFICE AREA CORRIDOR
3. PROVIDE SERVICE DISCONNECT FOR ALL SPLIT
SYSTEMS 110V OR HIGHER
4. SIZE CONDENSATE PER C.O.T AMENDMENT