Permit: T08CM03466

Parcel: 11901076A


Addresses:

3372 S 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03466

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/28/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ALL VDV CABLING TO BE SUPPORTED AND PROTECTED FROM PHYSICAL DAMAGE
2. PLEASE PROVIDE A LETTER FOR ALL LIGHTING CHANGES
05/18/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/18/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK EM AND EXIT LIGHTING
05/15/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CORDS NOT ALLOWED ABOVE CEILING -- 400.7 AND 8
2. SEAL UNUSED OPENINGS -- CONDUITS AND BOXES
3. BOND AT CONCENTRICS -- 250.97

OK BAKERY TESTING
05/14/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
MAINTAIN WORKING CLEARANCES - "LDS"

OK PANELS LDS, LA, B, CW, CC, CK, C, DK, CF, HDS, XFMR LDS
05/08/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/07/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PROTECT ALL TEMPORARY CONDUCTORS
2. A/C TO HAVE DISCONNECTING MEANS
3. BOXES MORE THAN 1/4" BOX TO SURFACE - 314.20
4. CLOSE ALL ELECTRIC IN TEMP AREA
5. FINISH VDV CABLING IN SERVER ROOM AS DISCUSSED
05/06/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/04/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ROOMS AS DISCUSSED
05/01/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VDV TO BE INDEPENDENTLY SUPPORTED
300.11, 725.24, 800.24, 760.24
2. ATTACH FIXTURES TO GRID SECURELY - 410.16
3. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE - 314.20
4. SEAL WALK-IN BOX RACEWAYS PER 300.7
5. PLEASE VERIFY LISTING AND LABELING PER 90.7 & 110.3 OF ALL EQUIPMENT
6. AN NRTL WILL NEED TO DO A FIELD EVALUATION OF BUSS AND LUG REPLACEMENT TO MAIN SWITCH BOARD
7. CONDUCTOR TO ENTER VERTICAL SECTION
TERMINATED IN 408.3
8. VERIFY DERATING PER 310.15