Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03466
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/28/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ALL VDV CABLING TO BE SUPPORTED AND PROTECTED FROM PHYSICAL DAMAGE 2. PLEASE PROVIDE A LETTER FOR ALL LIGHTING CHANGES |
|
05/18/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/18/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK EM AND EXIT LIGHTING |
|
05/15/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CORDS NOT ALLOWED ABOVE CEILING -- 400.7 AND 8 2. SEAL UNUSED OPENINGS -- CONDUITS AND BOXES 3. BOND AT CONCENTRICS -- 250.97 OK BAKERY TESTING |
|
05/14/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/11/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* MAINTAIN WORKING CLEARANCES - "LDS" OK PANELS LDS, LA, B, CW, CC, CK, C, DK, CF, HDS, XFMR LDS |
|
05/08/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/07/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PROTECT ALL TEMPORARY CONDUCTORS 2. A/C TO HAVE DISCONNECTING MEANS 3. BOXES MORE THAN 1/4" BOX TO SURFACE - 314.20 4. CLOSE ALL ELECTRIC IN TEMP AREA 5. FINISH VDV CABLING IN SERVER ROOM AS DISCUSSED |
|
05/06/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
05/04/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ROOMS AS DISCUSSED |
|
05/01/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VDV TO BE INDEPENDENTLY SUPPORTED 300.11, 725.24, 800.24, 760.24 2. ATTACH FIXTURES TO GRID SECURELY - 410.16 3. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE - 314.20 4. SEAL WALK-IN BOX RACEWAYS PER 300.7 5. PLEASE VERIFY LISTING AND LABELING PER 90.7 & 110.3 OF ALL EQUIPMENT 6. AN NRTL WILL NEED TO DO A FIELD EVALUATION OF BUSS AND LUG REPLACEMENT TO MAIN SWITCH BOARD 7. CONDUCTOR TO ENTER VERTICAL SECTION TERMINATED IN 408.3 8. VERIFY DERATING PER 310.15 |