Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03466
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/18/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ROOF: 1. MAINTAIN WORKING CLEARANCES 110.26 2. PROTECT CONDUCTORS IN A/C DISCONNECTS 3. SUPPORT COAX OFF ROOF 815 AND 820 STORE: 1. FINISH PREVIOUS MARKED ITEMS OK SOFT START RECEIVED CK#1108 -- $150.00 |
|
05/15/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK 2 X 4'S BREAK ROOM 2) FINISH VDV CABLING |
|
05/13/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* KITCHEN: 1) MAINTAIN WORKING CLEARANCES 110.26 2) BOXES OVER FILLED 3) FINISH WALK IN 300.7 4) FINISH INTER LOCK 5) FINISH SEPERATING CONDUIT NORTH EAST END 6) OK RE-CONNECTION OF CONDUCTORS MAIN SES 7) OK REFRIDGERATION CASES |
|
05/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LIQUOR STORE: 1) REMOVE ABANDONED VDV CABELING 724.3 AND 800.3 2) SEAL WACK IN BOX PER 300.7 ------------------------------------------------------------------------------------------------- CHECK STANDS: 1) BOND ENCLOSURE 2) FILL UNUSED OPENINGS IN ENCLOSURE 3) CONTRACTOR TO MAINTAIN LO/TO |
|
05/11/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CORDS NOT ALLOWED IN WALL OR ABOVE HARD CEILINGS 400.7 & 8 |
|
05/07/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
05/06/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. WILL CHECK ON DISCONNECTING MEAN FOR ROOM A/C 2. VERIFY IF EM LIGHTS IN HALL WORK 3. FINISH SERVER ROOM |
|
05/04/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/01/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
04/23/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT M/C CABLE AS PER 330.30 12" + 6' 2) SUPPORT VDV CABELING 725.64, 760.25, 800.24, 300.11 3) SUPPORT EMT 3' + 10' 4) OK CHEESE ISLAND AND BATHROOMS HARD LIDS AFTER CORRECTION |
|
04/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS LIQUOR ROOM |
|
04/03/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/03/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* MEAT PREP AREA FREEZER OK EAST WALL BAKERY OK LIQUOR AREA OK |
|
03/27/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS RESTROOMS |
|
03/18/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :$ GROUND SCREWS AND EMT HAS BEEN STRAPPED ALL OK |
|
03/17/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO TIGHTEN CONNECTORS BOXES 2. NEED K.O SEALS 3. NEED TO STRAP CONDUIT IN WALLS |
|
03/16/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SIGN WALL ELECTRICAL OK |
|
03/12/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |