Permit: T08CM03466

Parcel: 11901076A


Addresses:

3372 S 6TH AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03466

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/18/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ROOF:
1. MAINTAIN WORKING CLEARANCES 110.26
2. PROTECT CONDUCTORS IN A/C DISCONNECTS
3. SUPPORT COAX OFF ROOF 815 AND 820

STORE:
1. FINISH PREVIOUS MARKED ITEMS

OK SOFT START

RECEIVED CK#1108 -- $150.00
05/15/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK 2 X 4'S BREAK ROOM
2) FINISH VDV CABLING
05/13/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
KITCHEN:
1) MAINTAIN WORKING CLEARANCES 110.26
2) BOXES OVER FILLED
3) FINISH WALK IN 300.7
4) FINISH INTER LOCK
5) FINISH SEPERATING CONDUIT NORTH EAST END
6) OK RE-CONNECTION OF CONDUCTORS MAIN SES
7) OK REFRIDGERATION CASES
05/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
LIQUOR STORE:
1) REMOVE ABANDONED VDV CABELING 724.3 AND 800.3
2) SEAL WACK IN BOX PER 300.7
-------------------------------------------------------------------------------------------------
CHECK STANDS:
1) BOND ENCLOSURE
2) FILL UNUSED OPENINGS IN ENCLOSURE
3) CONTRACTOR TO MAINTAIN LO/TO
05/11/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORDS NOT ALLOWED IN WALL OR ABOVE HARD CEILINGS
400.7 & 8
05/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WILL CHECK ON DISCONNECTING MEAN FOR ROOM A/C
2. VERIFY IF EM LIGHTS IN HALL WORK
3. FINISH SERVER ROOM
05/04/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
05/01/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/23/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/14/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT M/C CABLE AS PER 330.30 12" + 6'
2) SUPPORT VDV CABELING 725.64, 760.25, 800.24, 300.11
3) SUPPORT EMT 3' + 10'
4) OK CHEESE ISLAND AND BATHROOMS HARD LIDS AFTER CORRECTION
04/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS LIQUOR ROOM
04/03/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/03/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MEAT PREP AREA FREEZER OK
EAST WALL BAKERY OK
LIQUOR AREA OK
03/27/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS RESTROOMS
03/18/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :$
GROUND SCREWS AND EMT HAS BEEN STRAPPED ALL OK
03/17/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO TIGHTEN CONNECTORS BOXES
2. NEED K.O SEALS
3. NEED TO STRAP CONDUIT IN WALLS
03/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SIGN WALL ELECTRICAL OK
03/12/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*