Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03449
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES WILL CHECK ROOFTOP CORRECTIONS ON FINAL |
|
11/24/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE A PLATE STRAP AT DRYER VENT 2. INSTALL FLEX DUCTS PER DETAILS ON PLANS 3. HIGH EFFICIENCY TAKE-OFF's REQUIRED AT ALL CONNECTIONS TO MAIN TRUNK LINES 4. INSULATE BOOTS (TAKE-OFF's) 5. REMOVE FOIL TAPE FROM DRYER VENT ON ROOF AND SEAL WITH OUTDOOR SEALANT OR OUTDOOR TAPE 6. SHORT POP RIVETS CAN BE USED ON CONNECTIONS 7. RELOCATE EXISTING CONDENSATE DRAIN TO TERMINATE WITH NEW DRAIN LINE. |