Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03431
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
11/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED SEALS FOR CONDUITS ABOVE PANEL 2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANELS 3. FILL UNUSED OPENING IN PANEL 4. PLEASE VERIFY CLASSIFIED LISTINGS FOR THIS PANEL AND BREAKERS NEED CTL TYPE 5. PLEASE VERIFY EXISTING CONDITIONS FOR INSTA-HOTS APPEARS NOT TO BE AS PER CODES 6. EM & EXITS NOT AS PER 700.12 (F) |