Permit: T08CM03431

Parcel: 10821328B

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/26/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/12/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE EXCEPT AS NOTED
1. SEAL UNUSED OPENING/CONDUIT ABOVE PANEL
2. NEED ITEMS FROM PREVIOUS INSPECTION FOR FINAL
11/10/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED TO PUT K.O SEALS IN BOXES
2. SEISMIC WIRES TO HOLD 2-4 LITES
3. NEED CIRCUITS FOR EXITS