Permit: T08CM03429

Parcel: 13316031C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/24/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/22/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/19/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/24/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A DUCT SMOKE DETECTION SYSTEM FOR EACH FAN COIL IN THE PLENUM CEILING. THE SUM OF THE TOTAL CFM IN THE PLENUM EXCEEDS 2000 CFM. SEE YOUR ENGINEER FOR DIRECTION