Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/24/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/22/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/19/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/24/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE A DUCT SMOKE DETECTION SYSTEM FOR EACH FAN COIL IN THE PLENUM CEILING. THE SUM OF THE TOTAL CFM IN THE PLENUM EXCEEDS 2000 CFM. SEE YOUR ENGINEER FOR DIRECTION |