Permit: T08CM03425

Parcel: 14111002B

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T08CM03425

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
02/02/2011 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
03/26/2010 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) OK 4" STUB UP INTO CT CABINET
2) OK GROUND RODS
09/03/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1. OK 1-4" PVC FROM TEP XFMR TO BUILDING HAVE 270 DEG. OF BENDS
2. PLAN CALLS FOR 2 - 4" RACEWAYS - NEED TO INSTALL PER PLANS OR REVISE PLANS
3. INSTALL WARNING RIBBON PER NEC 300.5
09/02/2009 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) MISSING ELECTRIC SHEETS IN PROVIDED PLANS
2) HAVE 4-90 DEGREE BENDS IN RACEWAY EQUALS 360 DEGREE OF BENDS. CANNOT HAVE MORE THAN 360 DEGREE OF BENDS. STILL NEED TO 90 DEGREE AT BENDS. STILL NEED TO 90 DEGREE UP TO BLDG THIS WILL HAVE AT A MINIMUM OF 5-90 DEGREE BENDS