Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T08CM03425
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2011 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 03/26/2010 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) OK 4" STUB UP INTO CT CABINET 2) OK GROUND RODS |
|
| 09/03/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. OK 1-4" PVC FROM TEP XFMR TO BUILDING HAVE 270 DEG. OF BENDS 2. PLAN CALLS FOR 2 - 4" RACEWAYS - NEED TO INSTALL PER PLANS OR REVISE PLANS 3. INSTALL WARNING RIBBON PER NEC 300.5 |
|
| 09/02/2009 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MISSING ELECTRIC SHEETS IN PROVIDED PLANS 2) HAVE 4-90 DEGREE BENDS IN RACEWAY EQUALS 360 DEGREE OF BENDS. CANNOT HAVE MORE THAN 360 DEGREE OF BENDS. STILL NEED TO 90 DEGREE AT BENDS. STILL NEED TO 90 DEGREE UP TO BLDG THIS WILL HAVE AT A MINIMUM OF 5-90 DEGREE BENDS |