Permit: T08CM03403

Parcel: 105110660

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM03403

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/06/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FOR CEILING TILES MECH. ONLY
02/27/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
02/26/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE SUPPLY DUCT AND INSTALL PER NOTE G-3
2. MO.2 3.3 D SEAL ALL DUCT WITH SEALANT TAPE NOT APPROVED
3. PROVIDE FLEX CONNECTOR AT PLENUM DROPS PER 3.3 I
4. FLEXIBLE EXHAUST DUCT TORN
5. FLEX NOT TO EXCEED 6' PER DETAILS M4.0 1, 2, 3
6. PROVIDE VIBRATION ISOLATORS PER DETAIL 9
7. PROVIDE 45 DEG. BRANCH TAPS PER DETAIL 4
8. PROVIDE SPIN IN TAPS PER DETAIL 3
9. ALL TAPS ARE TO BE SEALED WITH DUCT SEALER