Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM03403
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/06/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES MECH. ONLY |
|
02/27/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
02/26/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE SUPPLY DUCT AND INSTALL PER NOTE G-3 2. MO.2 3.3 D SEAL ALL DUCT WITH SEALANT TAPE NOT APPROVED 3. PROVIDE FLEX CONNECTOR AT PLENUM DROPS PER 3.3 I 4. FLEXIBLE EXHAUST DUCT TORN 5. FLEX NOT TO EXCEED 6' PER DETAILS M4.0 1, 2, 3 6. PROVIDE VIBRATION ISOLATORS PER DETAIL 9 7. PROVIDE 45 DEG. BRANCH TAPS PER DETAIL 4 8. PROVIDE SPIN IN TAPS PER DETAIL 3 9. ALL TAPS ARE TO BE SEALED WITH DUCT SEALER |