Permit: T08CM03403

Parcel: 105110660

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03403

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
UNLISTED EQUIPMENT HAS BEEN REMOVED FROM SITE
03/13/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ALL EQUIPMENT TO BE LISTED & LABELED - PLEASE VERIFY
2. PLEASE VERIFY EQUIPMENT IS LISTED AS APPLIANCES/MAINTAIN WORKING CLEARANCES - 110.26
3. PLEASE LABEL EQUIPMENT
4. BOXES MORE THAN 1/4" -- 314.20
5. GROUND HEATER ENCLOSURES
6. SUPPORT VDV CABLING -- 725.24
7. CORRECTLY LABEL PANEL DIRECTORY -- 408.4