Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/17/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* UNLISTED EQUIPMENT HAS BEEN REMOVED FROM SITE |
|
| 03/13/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL EQUIPMENT TO BE LISTED & LABELED - PLEASE VERIFY 2. PLEASE VERIFY EQUIPMENT IS LISTED AS APPLIANCES/MAINTAIN WORKING CLEARANCES - 110.26 3. PLEASE LABEL EQUIPMENT 4. BOXES MORE THAN 1/4" -- 314.20 5. GROUND HEATER ENCLOSURES 6. SUPPORT VDV CABLING -- 725.24 7. CORRECTLY LABEL PANEL DIRECTORY -- 408.4 |