Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03393
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL BOX EXTENDERS WHERE NEEDED PER NOTES LAST INSPECTION, LEAVE DEVICE PLATES OFF TO VERIFY |
|
12/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE INSTALLATION OF DEVICE COVER PLATES 2. INSTALL BOX EXTENDERS WHERE MORE THAN 1/4" GAP BETWEEN DRYWALL SURFACE & P-RING PER NEC |
|
12/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MC CABLE CANNOT BE SUPPORTED TO OTHER CONDUITS 2. MC CANNOT BE RUN INSIDE WALL STUD CHANNELS UNLESS A MIN. DISTANCE OF 1 1/2" BETWEEN STUD FACE & CABLE PER 330 NEC |