Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03375
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BOX BRACKETS OK MC STRAPPING OK MC CONNECTORS PLASTIC HAS BEEN REMOVED OK |
|
01/08/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO KEEP MC CABLE 1 1/4 FROM EDGE OF STUD 2. MC CABLE NEEDS PLASTIC INSULATIONS REMOVED BEFORE PUTTING CONNECTOR 3. BOX BRACKETS TO BE INSTALLED IN AN APPROVED METHOD |