Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/08/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALLS 2. CANNOT CUT CORD CUPS OFF OF SHOP LIGHTS NEED TO PLUG INTO RECEPTACLE |
|
04/20/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PVC CONDUIT RUN EXPOSED TO BE SCHEDULE 80 2. GROUNDS IN BOXES TO BE PROPERLY SPLICED WITH WIRE NUTS OR CRIMPS 3. PVC TO TERMINATE INTO JUNCTION BOX WITH A CONNECTOR 4. RECEPTACLES IN SHED TO BE GFI PROTECTED 5. ROMEX IN SHED TO BE PROTECTED FROM PHYSICAL DAMAGE. ARE WALLS TO BE COVERED ON INSIDE? 6. OK UNDERGROUND BETWEEN BUILDINGS. |