Permit: T08CM03342

Parcel: 122183300


Addresses:

3555 E LEE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/07/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
12/22/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
NO ACCESS AT 9:17 AM
12/10/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE READ AND FOLLOW NOTES
FROM 11/28/08 INSPECTION

NOTE: PLUMBERS TAPE IS NOT APPROVED FOR HANGING PIPING. SEE YOUR PLAN AND INSTALL FOR IT.
PIPE CANNOT SUPPORT THE EXPANSION TANK.
FAILURE TO MAKE CORRECTIONS WILL RESULT IN REINSPECTION FEES ON FUTURE INSTALLATIONS.
11/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. T&P RELIEF DRAIN TO BE GRAVITY DRAIN - NO BACKPITCH
2. NONE OF THE PIPING IS SECURE
3. PLAN SHOWS DRAIN VALVE EACH SIDE OF CIRC. PUMP
4. PLAN SHOWS CHECK VALVE ETC. ON PANEL SUPPLY
5. EXPANSION TANK NOT SUPPORTED