Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/16/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) ITEMS 3,6 & 7 STILL NOT COMPLETE 2) A REFEE MAYBE ASSESSED FOR UN-NECESSARY INSPECTIONS |
|
| 11/03/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH PREVIOUS ITEMS 2,3,4,6,7,8 & 9 |
|
| 09/21/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SECURE NM CABLE TO BOXES WITH APPROVED DEVICES 2) SECURE FIXTURES PER 410.16 3) RISER SUPPORTS TO BE ATTACHED TO JOIST 4) USE APPROVED SECURING METHODS 5) CORRECTLY IDENTIFY GROUNDED CONDUCTOR 6) VERIFY DERATING OF CONDUCTORS AT PANEL 7) PROPERLYN INSTALL FITTINGS 8) VERIFY JUNCTION BOX FILL 9) FINISH #1 & 6 PREVIOUS INSPECTION 10) NEED PERMANENT METAL ADDRESS LABELS AT SERVICES 11) PLEASE VERIFY QUALIFIED ELECTRICIAN 12) WHAT ARE UF CABLES AT BLOCK WALL OUTSIDE ? 13) AS BUILT PLANS NOT REFLECTIVE OF WORK INSTALLED 14) NEED ADDRESS POSTED ON BLDG |
|
| 09/18/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The inspector was unable to locate the job.| 945* 1) NO ADDRESS POSTED, CANNOT LOCATE |
|
| 09/15/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ARC-SHIELDS AND PROPER SCREWS FOR OUTLET AND SWITCHES 2) NEED COVER PLATES 3) NEED LENS FOR 2/4 LIGHTS 4) NEED GFI FOR BATHROOM 5) NEED 2 BRACKETS FOR RISER 6) NEED TO SE BONDING AND GROUNDING SYSTEM |