Permit: T08CM03307

Parcel: 11107024A


Addresses:

3333 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/30/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/17/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/16/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. OK TO TILE CEILINGS MECHANICAL ONLY
2. WILL SPOT CHECK INSULATED BOOTS ON NEXT INSPECTION
12/08/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO SHEETROCK HARD LIDS
CONFIRMED 2" DUCT LINER ON ROOF
12/05/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/02/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO COVER CONDENSATE IN WALL
12/01/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
DUCT IN RESTROOM AREA NOT INSTALLED
NOTE: DUCT SPLIT WITH ROOF JOIST WILL BE ALLOWED, PROVIDED THERE IS ENOUGH VOLUME TO MEET BALANCE REQUIREMENTS SET FORTH IN MECHANICAL SPEC. 3.03 M-1

ALL ROOFTOP DUCT IS TO BE INSULATED TO A MIN. OF R-8 (2") PER I.E.C.C

REFER TO DETAIL 102 M-3 FOR ROOFTOP DUCT SUPPORT
(SEE NOTE 1.05)
11/28/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*