Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2008 | ELECTRIC - FINAL | Approved | ||
| 12/30/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1) SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 2) SEAL TITE SEPERATED FROM DISCONNECT FITTING A/C-1 3) SUPPORT NEW SEAL TIGHT ACCROSS BACK ROOF INTERIOR: 1) FINISH SUPPORTING VDV CABELING 725.24, 800.24 AND 300.11 2) WAITING ON PALN REVISIONS 3) OPEN MORE TILES TO INSPECT VDV CABLES |
|
| 12/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. GROUND JUNCTION BOX 2. NEED MAINTENANCE RECEPTACLE ON ROOF 3. MAINTAIN WORKING CLEARANCES 110.26 INTERIOR: 1. FINISH VDV CABLING 2. PLANS NOT CORRECT FOR FEEDER TO BACK BUILDING 3. NEED PERMANENT PANEL SCHEDULE AS PER 408.4 |