Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T08CM03292

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
11/24/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) EXCLUDES ITEM #4 ON CORRECTION LIST
11/19/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE FULL RADIUS BENDS AT ALL FLEX DUCT
2) CHANGES OF DIRECTION, DO NOT KINK, PINCH, FLATTEN OR OTHER WISE RESTRIC AIR FLOW SEE DETAIL 104
3) PROVIDE E2-TRAP AND ALARM AS OUTLINED IN DETAIL 101-M.2
4) VERIFY INSULATION UNDER CONDENSER UNIT PRIOR TO COVERING CURB