Permit: T08CM03290

Parcel: 125170380


Addresses:

3827 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/27/2008 ELECTRIC - FINAL Approved
10/24/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SUPPORT MC CABLES ABOVE PANEL
2. TERMINATE GROUNDING EQUIPMENT CONDUCTORS AT BAR PER MANUFACTURES INSTRUCTIONS
3. WHITE CANNOT BE USED AS AN UNDERGROUND CONDUCTOR IN A RACEWAY
4. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS
5. REVISE PLAN TO REFLECT WORK DONE OR NOT DONE

OK TO TILE