Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED CHLORING AND BACTERIA REPORT |
|
| 12/31/2008 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE APPROVED SUPPORT FOR EXPANSION TANK 2) COMPLETE LIST FROM 12/29/08 |
|
| 12/29/2008 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL VACUUM RELIEF VALVE AT WATER HEATER PER PLAN 2) INSTALL PAN DRAIN FOR WATER HEATER PER PLAN 3) INSTALL SUPPORT AND SECURE WATER HEATER EXPANSION TANK 4) PROVIDE STERILIZATION AND BACTERIA REPORT FOR POTABLE WATER IN BLDG PER PLAN 5) COMPLETE INSULATION AT WATER HEATER 6) PROVIDE FACTORY TAPPED CLEANOUT PLUGS WITH MACHINE SCREWS AT CLEANOUTS |