Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM03271
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/31/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) POWER POLES WILL BE DONE LATER ON TENANT PERMIT, EM LIGHTING ON SAME PERMIT AS TENANT |
|
12/29/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VDV CABELING TO BE PER 725.4-24, 800.3-24 300.11 2) CORDS NOT ALLOWED ABOVE CEILING 406.7-8 3) INSTALL POWER POLES 4) EM LIGHTING NOT PER PLAN, PLEASE PROVIDE LETTER FOR CHANGES 5) SHEET METAL SCREWS NOT FOR GROUNDING 250.8 6) DISCONNECT MOUNTED ON ACCESS PANEL 440.14 7) MAINTAIN WORKING CLEARANCES 110.26 8) PROPERLY BOND AND GROUND ENCLOSURES 250.8 MULTIPLE CONDUCTORS 9) DETERIORATED SEAL TIGHT NEEDS TO BE REPLACED 10) MAINTENANCE RECEPTACLE TO BE GFI 210.63 11) EM LIGHTING TO BE PER CODE 700.12F 12) CONDUIT OUT OF PANEL NEEDS TO BE PLUGED 13) CLEAN SURFACE UNDER GROUND BOX 250.12 |