Permit: T08CM03260

Parcel: 130030270


Addresses:

2708 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/21/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/10/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) #5 CIRCUIT SHALL BE ON #12 WIRE
2) FAMILY ROOM OK WITH 14-2
3) ALLOW GROUND TAIL TO GROUND ALL ELECTRICAL SWITCHES AND OUTLETS
4) MAKE UP ALL BOXES, READY TO CONNECT SWITCHES AND OUTLETS
07/09/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND ALL METAL BOXES
2) CAN NOT MIX 12-2 AND 14-2 WIRE, CHECK PLAN FOR REQUIRED BREAKER AND WIRE SIZE