Permit: T08CM03250

Parcel: 10601247B


Addresses:

125 E PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/21/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/15/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED TO SEE COPPER INSULATED
DWV THRU ROOF OK
COPPER OK
05/07/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLASSROOM SINKS, SECOND FLOOR
N/H DWV VTR OK
WATER TEST OK
WATER PIPING OK
OK TO COVER THIS AREA ONLY
05/05/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER FIRST FLOOR
05/04/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
- PIPE INSULATION IN PREVIOUSLY INSPECTED
TOILET RMS. OK
- 135 DEG. MAX. CHANGE OF DIRECTION
- CLEANOUT EXTENSION
- PERM CAPS
- CLEARANCE AROUND MAIN WATER LINE,
FROM SPRINKLER PIPE
04/23/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 133-136 DWV WITH TEST OK
2) 143 + 144, 129-128, 147 + 148 DWV AND WATER WITH TEST OK. TEST ON 2ND LEVEL SINKS THRU TEST FITTINGS OK ADD SUPPORTS, OK TO INSULATE
04/10/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV & WATER W/TESTS RMS. 104 & 105
PER UNAPP. DRAWINGS
OK TO INSULATE SUBJECT TO APPROVED PLANS
ACCESS TO PERMITS AND PLANS SHALL BE PROVIDED
AT ALL TIMES.
03/12/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RESTROOMS #120, 121, 124, BREAKROOM SINK, HOSE BIBS AND ALL ASSOCIATED PIPING IN THIS AREA OK
NEED TO CHECK INSULATION ON HOT AND RETURN PIPING