Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2009 | ELECTRIC - PROGRESS | Approved | ||
| 08/19/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/11/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/01/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 05/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 04/28/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. OK RECEPTION AREA SOFFITS 1ST FLOOR 2. WILL NEED TO POST BOND FOR TEMP POWER TEST |
|
| 04/22/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. GFI MAIN TEST PER 230.96 NEC 2. LETTER OF TORQUE 3. BUSHINGS ON CONDUITS IN SES PER 352.300.5 NEC 4. BOND BLD. STEEL, GAS, WATER 4. OK WALLS 1ST FLOOR CLASSROOMS AND RESTROOMS |
|
| 04/07/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* ROOM 125, 106, 109, 113, 105, 102 RESTROOM, WALLS OK |
|
| 03/19/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 03/13/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 03/06/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK NEXT 40' FROM LAST INSPECTION |
|
| 02/27/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 02/23/2009 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. OK FINAL LIFT WEST END CLASSROOMS 2. OK U.G. TO ACTIVITY RM (MUSTANG ROOM) JUNCTION BOXES @ WEST END OF BUILDING 3. NEED GROUNDING ELECTRODE SYSTEM @ ACTIVITY BUILDING 4. VERIFY WITH ENGINEER IF DISCONNECTING MEANS ARE NEEDED @ SEPARATE STRUCTURES NEC 225 |