Permit: T08CM03250

Parcel: 10601247B


Addresses:

125 E PRINCE RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T08CM03250

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
07/22/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) NEC 110-26 CLEARANCE
2) CALL FOR PARKING LTG INSPECTION WHEN WIRING TERMINATED
06/19/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
24" MIN. DEPTH FOR DRIVEWAYS, PARKING -- PER 300.5 NEC
03/19/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 1 - 4" AND 2 - 2" PVC CONTINUATION
BUILDING OUT STREET CURB
03/06/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK NEXT 40' FROM LAST INSPECTION
02/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 1 - 4" AND 4 - 2" PVC FROM EXISTING CLASSROOMS HEADING SOUTHEAST 50'
2. OK GROUND RODS @ SES LOCATION
02/23/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
02/05/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
01/27/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
CHILLER ROOM 2 - 4" FOR CHILLERS, 2 - 3" FOR CP-PANEL FOR CHILLER 1 - 1 1/4 - 1 - 1" - 1 - 3/4 ALSO FOR CP-PANEL
COOLING TOWER 3 - 3/4 SPARES 1 - 1', 1 - 1 1/4 AND 1 3/4
ON WEST WALL ADMIN. BUILDING PIPE IN WALLS OK
01/20/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK PVC CONDUITS UNDER SLAB CLASSROOMS
01/15/2009 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. PROVIDE PHYSICAL PROTECTION FOR FEEDER TO TRAILER
ALSO AT RISER
2. OK PVC CONDUITS UNDER SLAB ADMIN. BLDG.
3. OK 30' OF 3/0 ATTACHED TO REBAR