Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* MARKING TAPE TO ENCIRCLE CONDUCTOR |
|
| 02/04/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" - 314.20 2. USE APPROVED HARDWARE FOR DEVICES - NOT DRYWALL SCREWS 3. MAINTAIN WORKING CLEARANCES 110.26 SUB-PANEL 4. PANEL DIRECTORY PER 408.4 BOTH MAIN AND SUB-PANEL 5. SECURE CABLE TO BACK OF DISCONNECT 312.5 6. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 7. FEEDER CONDUIT LOCK NUT BACKWARDS 8. TIGHTEN CONDUCTOR TERMINATIONS 9. TIGHTEN WATER HEATER FITTINGS |