Permit: T08CM03248

Parcel: 12504034A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/09/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
MARKING TAPE TO ENCIRCLE CONDUCTOR
02/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" - 314.20
2. USE APPROVED HARDWARE FOR DEVICES -
NOT DRYWALL SCREWS
3. MAINTAIN WORKING CLEARANCES 110.26 SUB-PANEL
4. PANEL DIRECTORY PER 408.4 BOTH MAIN AND SUB-PANEL
5. SECURE CABLE TO BACK OF DISCONNECT 312.5
6. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS
7. FEEDER CONDUIT LOCK NUT BACKWARDS
8. TIGHTEN CONDUCTOR TERMINATIONS
9. TIGHTEN WATER HEATER FITTINGS