Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03244
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC SUBJECT TO APPROVAL OF AS BUILTS 2) MANAGER RESPONSIBLE FOR FINISH VDV CABLING 3) PERMIT NEEDED FOR 3 NEW CANS AT MENU BOARD NOTE #8 |
|
| 10/01/2009 | ELECTRIC - FINAL | Cancelled | CANCELLED PER CHRIS #480-252-1334 | |
| 10/01/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 09/10/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH ITEMS 1,2,3 & 7 PREVIOUS INSPECTION 2) VDV CABLING THAT HAS BEEN ABANDONED TO BE REMOVED FOR FIRE SAFETY 725.3 AND 800.3 3) MINI LOW VOLTAGE LIGHTING ADDED ABOVE SIGN-NOT ON PLANS |
|
| 06/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NO WORK PROGRESS - A REFEE NEEDS TO BE PAID BEFORE NEXT INSPECTION |
|
| 05/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLES ABOVE CEILING AS PER 300.11, 334.30 2. SUPPORT VDV CABLING AS PER 725.24, 800.24, 300.11 3. EXPOSED CONDUCTORS 4. LABEL PANEL AS PER 408.4 5. FILL UNUSED OPENINGS IN PANEL ENCLOSURE 6. MAIN SWITCHBOARD NOT PROPERLY LABELED 7. PLANS STILL NOT REFLECTIVE OF WORK INSTALLED 8. FINISH PREVIOUS ITEMS *UNNECESSARY INSPECTIONS MAY RESULT IN REFEE |
|
| 03/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW PANEL "C" NOT LABELED, WIRE SIZE AND BUS NOT PER PLAN, CIRCUITING NOT PER PLAN 2. FLEX NOT SUPPORTED PER CODE, MC NOT SUPPORTED PER CODE, J-BOX NOT SUPPORTED 3. REMOVE/ABANDON ALL UNUSED ELECTRICAL CONDUIT WIRING SEE NOTES E-1 PLANS |