Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03243
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
12/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/23/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER STEVE 955-1899 | |
12/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
12/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH VDV CABLING PREVIOUS ITEM CORRECTED |
|
12/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* NO WORK PROGRESS |
|
12/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT MC CABLES ABOVE CEILING AS PER 330.30 & 300.11 2. SUPPORT VDV CABLING AS PER 725.3 & 24, 800.3 & 24, 300.11 3. PANEL SCHEDULE TO BE AS PER 408.4 -- ALSO, LEGIBLE PLEASE TYPE OR PRINT CLEARLY 4. FILL UNUSED OPENINGS IN JUNCTION BOXES 5. OPEN JUNCTION BOXES 6. USE APPROVED MEANS & METHODS TO SUPPORT MC CABLE 7. BOXES 314.20 & 21 |