Permit: T08CM03243

Parcel: 11309225A


Addresses:

801 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/31/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
12/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/23/2008 ELECTRIC - FINAL Cancelled CANCELLED PER STEVE 955-1899
12/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
12/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH VDV CABLING

PREVIOUS ITEM CORRECTED
12/04/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
NO WORK PROGRESS
12/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT MC CABLES ABOVE CEILING AS PER 330.30 & 300.11
2. SUPPORT VDV CABLING AS PER 725.3 & 24, 800.3 & 24, 300.11
3. PANEL SCHEDULE TO BE AS PER 408.4 -- ALSO, LEGIBLE PLEASE TYPE OR PRINT CLEARLY
4. FILL UNUSED OPENINGS IN JUNCTION BOXES
5. OPEN JUNCTION BOXES
6. USE APPROVED MEANS & METHODS TO SUPPORT MC CABLE
7. BOXES 314.20 & 21