Permit: T08CM03231

Parcel: 10603142A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T08CM03231

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CLOSET FLANGE OK
CALL 03090 FOR STERILIZATION
12/22/2008 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO EXTEND CLOSET BEND W/APPROVED COUPLING TO PROVIDE CORRECT SOLVENT WELD CONNECTION BETWEEN PIPE AND CLOSET FLANGE
2. LETTER FOR WALL BRACKET LAV INSTALLATION OK
12/15/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE STAMPED LETTER ALLOWING WALL HUNG LAVATORY
2. WILL NEED TO SEE CLOSET FLANGE
3. RECALL 03035 WHEN STERILIZING SYSTEM
SEE NOTE 21 ON P-1
11/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK TO COVER WALLS AFTER PROTECTING VENTS W/BANG PLATES AND PROVIDING SUPPORT FOR LAV.
- NOTE PLAN SPECS CARRIER. WILL INSP. CLOSET FLANGE AFTER FINISHED FLOOR, PRIOR TO SETTING WC