| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PANEL LABELING TO BE AS PER 408.4 - NO ABBREVIATION, LEGIBLE 2. BREAKERS AT SERVICE TO BE PROTECTED FROM WEATHER OK ROOF |
|
| 12/15/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CANS IN SOFFITS OK DEVICES OK IMC CONDUIT FOR GATE OPENER |
|
| 11/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH ELECTRIC |
|
| 11/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CABLES ABOVE PANEL & 12" OF BOXES 2. FIXTURE NOT ALLOWED AS A JUNCTION BOX 3. HAVE BUILDING INSPECTOR VERIFY FIREWALL SEPARATION 4. PROTECT NM CABLE AT STUDS 300.4 5. SECURE NM CABLES TO PANEL 312.5 6. PANEL LABELING TO BE AS PER 408.4 |