Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03214
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/07/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" (314.20) OR 1/8" (314.21) 2. PANEL DIRECTORY TO BE AS PER 408.4 - LEGIBLE & DISTINGUISHABLE FROM ONE ANOTHER - NO ABBREVIATIONS 3. MISSING RECEPTACLES IN ROOM 126 4. EM & EXIT LIGHTS TO BE ON CIRCUIT FOR AREA SERVED 700.12 (F) |