Permit: T08CM03214

Parcel: 115180220


Addresses:

1475 N ORACLE RD

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/12/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
10/13/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. FINISH VDV CABLING SUPPORTED INDEPENDENTLY & NOT FROM OTHER WIRING METHODS
2. SUPPORT WIRE NEEDED FOR EXIT & RELOCATED FIXTURES ALSO, ATTACHED TO GRID
3. BOX OVERFILLED

OK TO TILE EXCEPT AS NOTED

*NEED REVISION FOR LIGHTING FINAL
10/08/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*