Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM03213
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/02/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BOXES OK 2. KNOCKOUTS OK 3. STRAP MC OK 4. BOXES MADE UP OK |
|