Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/18/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/09/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO SERVICE DISCONNECT ON EXISTING SERVICE PANEL. NO NAMEPLATE DATA EXISTS FOR EXISTING SERVICE PANEL. EXISTING PANEL APPEARS TO BE 12 CIRCUIT WITH 125AMP BUSSING. HAVE PANEL BEING BACKFED WITH 40 AMP BREAKER FROM PV SYSTEM. PLAN CALLS FOR 200 AMP SERVICE WITH 200 AMP MAIN BREAKER. 2. OK ROOF TOP |
|
| 11/21/2008 | BUILDING - FINAL | Not ready for Inspection |